Precautions for tank placement
1) The fuel tank storage location must be safe to prevent fires. The fuel tank or oil drum should be placed separately in a visible place, properly away from the diesel generator set, and strict prohibition of smoking.
2) The fuel capacity in the fuel tank should be guaranteed daily supply.
3) After the fuel tank is placed, a daily fuel tank should be added between the large oil depot and the unit so that the pressure of direct oil supply is not more than 2.5 meters. Even during the shutdown of the diesel engine, the fuel is not allowed to flow into the diesel engine through the oil inlet line or the fuel injection line depending on gravity.
4) The resistance at the port must not exceed the values specified on all diesel performance data sheets when using clean cartridges. This resistance value is based on the fuel tank installed with half of the fuel.
5) The fuel return resistance should not exceed the specifications on the diesel performance data sheet.
6) The connection of the fuel return line should not cause a shock wave in the fuel in the tubing.